New RxMS logo

Z-Brick®

The Z-Brick® is a piece of test equipment to quickly check the condition and abilty of a feeder to deliver power under loaded conditions.

The monitor introduces a momentary load that gives the ability to measure the impedance of the incoming lines. This offers a way to quantify the ablity for a feeder to deliver power. It can easly identify problems including undersized feeds or poor connections.

Z-Brick® Technical Documents

Specification Sheet

User Manual

Specifications

Table Header
POWER SOURCE
Power Requirements
100V-240V ACrms +/-10% 47-63 Hz 18Watts
SYNCHRONIZING & SAMPLING
Sampling Frequency
128 samples/cycle
A/D Resolution
12 bit oversampled voltage 2X: current 4X
Auto 50/60 Hz; or locked to input
DETAILS
Accuracy
Voltage= 0.5% reading +/- 0.3Vrms error.
Current= 0.2% reading +/- 0.1 Arms error.
Impedance = 1% reading +/- 0.030mΩ error
TC = 0.001% / °C
Measurement Details
• Three phase or single phase measurements.
• Load bank = 40 Ohm delta non-inductive.
• Load estimate: 120v = 4.5Arms 208v / 3Phase = 9.1Arms 480v / 3Phase = 20.8Arms
• Non-linear impedance sources (UPS or regulator) will cause incorrect readings.
• Voltage flicker and high frequency noise can cause inaccurate results, recommended procedure is to take multiple readings.
PHYSICAL CHARACTERISTICS
Environmental & Safety
Operating environment: Indoors ; Operating Temperature: 0ºC to 40ºC (32F-104F) ; Operating Humidity: 80% Max Non-Condensing ; Conforms to IEC61010 CAT III 600V
Size
Dimensions: 11.5 x10.25 x 4 Inches. (Height x Width x Depth)
Weight
5.9 Lbs